6 INTERPRETATION OF THE RESULTS
Under the conditions where controls were carried out (operating rooms at rest):
raised particulate concentrations in the operating rooms OP2, OP3, OP4 and OP5 correspond
to the criteria of classification of class 1000 (room of surgical operation of normal
type).
Particulate concentrations raised in operating rooms OP1 correspond to the criteria
of classification of classify 100 (room of surgical operation, orthopedic or cardio
vascular).
Particulate concentrations raised in the room of operation OP3:
- Room at rest > = 5,0 µm: 25.4 particles / cubic foot
- Room at rest = 0.5 µm: 512 particles / cubic foot
Room at rest with startup of the system ions with level of the mouths of blowing:
- >= 5,0 µm: 15 particles / cubic foot
- <= 0.5 µm: 153 particles / cubic foot
The installation of the system " ions " show an improvement of approximately 70
% of the quality of the air for the particles of 0.5 µm
The particulate kinetics of decontamination to 0.50 µm (system " ions") corresponds
to the criterion of classification CP(0.5 20.